Table 3-1. Recommended Sizes for Input
Conductors and Line Fuses
*Sized per National Code for 80 °C rated copper conductors @ 30 °C ambient. Not
more than three conductors in raceway or cable. Local codes should be followed if they
specify sizes other than those listed above.
3.0. INSTALLATION
A. LOCATION
A proper installation site is necessary for the power source to provide depend-
able service. A proper installation site permits freedom of air movement through
the unit while minimizing exposure to dust, dirt, moisture, and corrosive vapors.
A minimum of 18 inches (46 cm) is required between the side and rear panels
of the power source and the nearest obstruction.
The selected site should also allow easy removal of the power source outer
enclosure for maintenance. See Table 2-1 for overall dimensions of the unit.
B. RECEIVING, UNPACKING AND PLACEMENT
When requesting information concerning this equipment, it is essential that
Item number, Serial number and Model number of the equipment be supplied.
1. Upon receipt, remove all packing material and carefully inspect for any
damage that may have occurred during shipment. Any claims for loss
or damage that may have occurred in transit must be filed by the
purchaser with the carrier. A copy of the bill of lading and freight bill will
be furnished by the carrier on request.
2. Remove the power source from the container. Remove all packing
materials. Check the container for any loose parts.
3. Check air passages at front and rear of cabinet, making sure that
packing material has not obstructed air flow through the power source.
4. Install the lifting bolt furnished with the power sources into the top of the
unit.
5. After selecting an installation site, place the power source in the desired
location. The unit may be lifted either by using the lifting bolt or by forklift
truck. If a forklift is used for lifting the unit, be sure that the lift forks are
long enough to extend completely under the base.
C. PRIMARY (INPUT) ELECTRICAL CONNECTION
This power source is a three-phase unit and must be connected to a three-
phase power supply. It is recommended that the unit be operated on a dedicated
circuit to prevent impairment of performance due to an overloaded circuit.
For lifting purposes and for keeping
dust, moisture, and other foreign ma-
terial from entering the power source,
the lifting eyebolt must be fully tight-
ened with a tool.
Do not use filters on this unit as they
would restrict the volume of intake air
required for proper cooling. Output
ratings on this unit are based on an
unobstructed supply of cooling air
drawn over its internal components.
Warranty is void if any type of filtering
device is used.
Rated Input
@ 100% Duty Cycle
Input &
GND
Conductor*
CU/AWG
Fuse
Size
Amps
Volts Amps
220
230
400
460
575
68
66
37
33
26
No. 6
No. 6
No. 8
No. 8
No. 10
100
100
60
60
50
SECTION 3 INSTALLATION